Each dual voltage direct current system must have a suitably sensitive ground detection system which indicates current in the ground connection, has a range of at least 150 percent of neutral current rating and indicates the polarity of the fault. [CGD 94-108, 61 FR 28276, June 4, 1996]Grounded Conductors
TL;DR
Each dual voltage direct current system must have a suitably sensitive ground detection system which indicates current in the ground connection, has a range of at least 150 percent of neutral current rating and indicates the polarity of the fault.
Section 111.05-29 — full text
Rendered cleanly from the source — the exact regulatory text, with subsection structure preserved.