-1 -1 Power ventilation systems except machinery space ventilation systems

The exact 46 CFR §111.103-1 text, rendered cleanly with its subsection structure — plus how this rule shows up on the exam.

Public-domain federal text · ingested from eCFR
Every answer cited & verifiedAll 4 USCG exam modulesReviewed by a former NMC exam writer

TL;DR

Each power ventilation system that is not a machinery space ventilation system must have:

Section 111.103-1 — full text

Rendered cleanly from the source — the exact regulatory text, with subsection structure preserved.

Each power ventilation system that is not a machinery space ventilation system must have:

(a)A control to stop the ventilation that is:

(1)Outside the space ventilated; and

(2)Grouped with the controls for every power ventilation system to which this section is applicable; and

(b)In addition to the control required by paragraph (a), a stop control that is:

(1)As far as practicable from the control required by paragraph (a) and grouped with the controls for every power ventilation system to which this section is applicable; or

(2)The circuit breakers for ventilation grouped on the main switchboard and marked, “In Case of Fire Trip to Stop Ventilation.” Note:The requirements of this section do not apply to closed ventilation systems for motors or generators, diffuser fans for refrigerated spaces, room circulating fans, or exhaust fans for private toilets of an electrical rating comparable to that of a room circulating fan. [CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by USCG-2020-0075, 88 FR 16365, Mar. 16, 2023]

(a)A control to stop the ventilation that is:

(1)Outside the space ventilated; and

(2)Grouped with the controls for every power ventilation system to which this section is applicable; and

(b)In addition to the control required by paragraph (a), a stop control that is:

(1)As far as practicable from the control required by paragraph (a) and grouped with the controls for every power ventilation system to which this section is applicable; or

(2)The circuit breakers for ventilation grouped on the main switchboard and marked, “In Case of Fire Trip to Stop Ventilation.” Note:The requirements of this section do not apply to closed ventilation systems for motors or generators, diffuser fans for refrigerated spaces, room circulating fans, or exhaust fans for private toilets of an electrical rating comparable to that of a room circulating fan. [CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by USCG-2020-0075, 88 FR 16365, Mar. 16, 2023]

From regulation to exam

See how this section shows up on the test

Test your knowledge

Try 5 real exam questions on the rules behind this regulation — no sign-up needed.

Was this page helpful?

Start drilling in 30 seconds. Free.

No signup, no credit card — answer 5 real, cited exam questions right now.

46 CFR §111.103-1 — -1 -1 Power ventilation systems except machinery space ventilation systems · CaptainsGround