(a) The current-carrying capacity of generator cables must not be:

Section 111.12-9 — full text

Rendered cleanly from the source — the exact regulatory text, with subsection structure preserved.

(a)The current-carrying capacity of generator cables must not be:

(1)Less than 115 percent of the continuous generator rating; or

(2)Less than 115 percent of the overload for a machine with a 2 hour or greater overload rating.

(b)Generator cables must not be in the bilges.