-10 -10 Ventilation

The exact 46 CFR §111.15-10 text, rendered cleanly with its subsection structure — plus how this rule shows up on the exam.

Public-domain federal text · ingested from eCFR
Every answer cited & verifiedAll 4 USCG exam modulesReviewed by a former NMC exam writer

TL;DR

(a)Each room, locker, and box for storage batteries must be arranged or ventilated to prevent accumulation of flammable gas.

Section 111.15-10 — full text

Rendered cleanly from the source — the exact regulatory text, with subsection structure preserved.

(a)Each room, locker, and box for storage batteries must be arranged or ventilated to prevent accumulation of flammable gas. (b)If power ventilation is required, the following must be met:

(1)The power ventilation system must be separate from ventilation systems for other spaces.

(2)Electric motors must be outside the duct and compartment and:

(i)Have an explosion-proof motor for a Class I, Division 1, Group B or its IEC equivalent designation of Zone 1, IIB + H2 location; or

(ii)Be at least 10 ft. (3 m) from the exhaust end of the duct.

(3)Each blower must have a non-sparking fan.

(4)The power ventilation system must be interlocked with the battery charger so that the battery cannot be charged without ventilation. (c)Each battery room for large battery installations must have a power exhaust ventilation system and have openings for intake air near the floor that allow the passage of the quantity of air that must be expelled. The quantity of the air expelled must be at least: (d)Each battery room or battery locker for moderate or small battery installations must have louvers near the bottom of the room or locker for air, and must be ventilated by:

(1)Ventilation that meets paragraph (c) of this section;

(2)An exhaust duct:

(i)That ends in a mechanically ventilated space or in the weather;

(ii)That extends from the top of the room or locker to at least 3 ft. (1 m) above the top of the room or locker;

(iii)That is at an angle of 45 degrees or less from the vertical; and

(iv)That has no appliances, such as flame arresters, that impede free passage of air or gas mixtures; or

(3)A duct from the top of the room or locker to an exhaust ventilation duct. (e)Except for a deck box for a small battery installation, each deck box must have a duct from the top of the box to at least 4 ft. (1.2 m) above the box ending in a gooseneck or mushroom head that prevents entrance of water. Holes for air must be on at least two parallel sides of each box. (f)Each deck box must be weathertight. (g)Each box for a small battery installation must have openings near the top to allow escape of gas. If the installation is in a non-environmentally-controlled location, the installation must prevent the ingress of water. q = 3.89(i)(n).where: q = quantity of expelled air in cubic feet per hour.i = Maximum charging current during gas formation, or one-fourth of the maximum obtainable charging current of the charging facility, whichever is greater.n = Number of cells.[CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by CGD 94-108, 61 FR 28278, June 4, 1996; USCG-2020-0075, 88 FR 16361, Mar. 16, 2023]

(1)The power ventilation system must be separate from ventilation systems for other spaces.

(2)Electric motors must be outside the duct and compartment and:

(i)Have an explosion-proof motor for a Class I, Division 1, Group B or its IEC equivalent designation of Zone 1, IIB + H2 location; or

(ii)Be at least 10 ft. (3 m) from the exhaust end of the duct.

(3)Each blower must have a non-sparking fan.

(4)The power ventilation system must be interlocked with the battery charger so that the battery cannot be charged without ventilation. (c)Each battery room for large battery installations must have a power exhaust ventilation system and have openings for intake air near the floor that allow the passage of the quantity of air that must be expelled. The quantity of the air expelled must be at least: (d)Each battery room or battery locker for moderate or small battery installations must have louvers near the bottom of the room or locker for air, and must be ventilated by:

(1)Ventilation that meets paragraph (c) of this section;

(2)An exhaust duct:

(i)That ends in a mechanically ventilated space or in the weather;

(ii)That extends from the top of the room or locker to at least 3 ft. (1 m) above the top of the room or locker;

(iii)That is at an angle of 45 degrees or less from the vertical; and

(iv)That has no appliances, such as flame arresters, that impede free passage of air or gas mixtures; or

(3)A duct from the top of the room or locker to an exhaust ventilation duct. (e)Except for a deck box for a small battery installation, each deck box must have a duct from the top of the box to at least 4 ft. (1.2 m) above the box ending in a gooseneck or mushroom head that prevents entrance of water. Holes for air must be on at least two parallel sides of each box. (f)Each deck box must be weathertight. (g)Each box for a small battery installation must have openings near the top to allow escape of gas. If the installation is in a non-environmentally-controlled location, the installation must prevent the ingress of water. q = 3.89(i)(n).where: q = quantity of expelled air in cubic feet per hour.i = Maximum charging current during gas formation, or one-fourth of the maximum obtainable charging current of the charging facility, whichever is greater.n = Number of cells.[CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by CGD 94-108, 61 FR 28278, June 4, 1996; USCG-2020-0075, 88 FR 16361, Mar. 16, 2023]

From regulation to exam

See how this section shows up on the test

Test your knowledge

Try 5 real exam questions on the rules behind this regulation — no sign-up needed.

Was this page helpful?

Start drilling in 30 seconds. Free.

No signup, no credit card — answer 5 real, cited exam questions right now.