(a) Each circuit that supplies a device on a switchboard, except a circuit under paragraph (b) of this section, must have overcurrent protection.

Section 111.30-17 — full text

Rendered cleanly from the source — the exact regulatory text, with subsection structure preserved.

(a)Each circuit that supplies a device on a switchboard, except a circuit under paragraph (b) of this section, must have overcurrent protection.

(b)A circuit that supplies a device on a switchboard must not have overload protection if it supplies:

(1)An electric propulsion control;

(2)A voltage regulator;

(3)A ship's service generator circuit breaker tripping control; or

(4)A device that creates a hazard to the vessel if deenergized.

(c)If short circuit protection is used in any of the circuits listed in paragraph (b) of this section, it must be set at not less than 500% of the expected current.

(d)A secondary circuit of a current transformer must not be fused, and the circuit from a current transformer to a device that is not in the switchboard must have a high voltage protector to short the transformer during an open circuit.

From regulation to exam

See how this section shows up on the test

Test your knowledge

Try 5 real exam questions on the rules behind this regulation — no sign-up needed.

Was this page helpful?

Start drilling in 30 seconds. Free.

No signup, no credit card — answer 5 real, cited exam questions right now.

46 CFR §111.30-17 — -17 -17 Protection of instrument circuits · CaptainsGround