-24 -24 Generation systems greater than 3000 kW

The exact 46 CFR §111.30-24 text, rendered cleanly with its subsection structure — plus how this rule shows up on the exam.

Public-domain federal text · ingested from eCFR
Every answer cited & verifiedAll 4 USCG exam modulesReviewed by a former NMC exam writer

TL;DR

Except on a non-self-propelled mobile offshore drilling unit (MODU) and a non-self-propelled floating Outer Continental Shelf facility, when the total installed electric power of the ship's service generation system is more than 3000 kW, the switchboard must have the following:

Section 111.30-24 — full text

Rendered cleanly from the source — the exact regulatory text, with subsection structure preserved.

Except on a non-self-propelled mobile offshore drilling unit (MODU) and a non-self-propelled floating Outer Continental Shelf facility, when the total installed electric power of the ship's service generation system is more than 3000 kW, the switchboard must have the following:

(a)At least two sections of the main bus that are connected by:

(1)A non-automatic circuit breaker;

(2)A disconnect switch; or

(3)Removable links.

(b)As far as practicable, the connection of generators and duplicated equipment equalized between the sections of the main bus. [CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by CGD 94-108, 61 FR 28279, June 4, 1996]

(a)At least two sections of the main bus that are connected by:

(1)A non-automatic circuit breaker;

(2)A disconnect switch; or

(3)Removable links.

(b)As far as practicable, the connection of generators and duplicated equipment equalized between the sections of the main bus. [CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by CGD 94-108, 61 FR 28279, June 4, 1996]

From regulation to exam

See how this section shows up on the test

Test your knowledge

Try 5 real exam questions on the rules behind this regulation — no sign-up needed.

Was this page helpful?

Start drilling in 30 seconds. Free.

No signup, no credit card — answer 5 real, cited exam questions right now.

46 CFR §111.30-24 — -24 -24 Generation systems greater than 3000 kW · CaptainsGround