-29 -29 Emergency switchboards

The exact 46 CFR §111.30-29 text, rendered cleanly with its subsection structure — plus how this rule shows up on the exam.

Public-domain federal text · ingested from eCFR
Every answer cited & verifiedAll 4 USCG exam modulesReviewed by a former NMC exam writer

TL;DR

(a) Each emergency generator must have an emergency switchboard.

Try a sample question — no sign-up

According to 46 CFR, where must the neutral of a grounded generation and distribution system be grounded?

Section 111.30-29 — full text

Rendered cleanly from the source — the exact regulatory text, with subsection structure preserved.

(a)Each emergency generator must have an emergency switchboard.

(b)There must be a test switch at the emergency switchboard to simulate a failure of the normal power source and cause the emergency loads to be supplied from the emergency power source.

(c)The emergency switchboard must be as near as practicable to the emergency power source but not in the same space as a battery emergency power source.

(d)Each switchboard of an alternating-current emergency generator must have:

(1)A circuit breaker that meets § 111.12-11;

(2)A disconnect switch or link for each emergency generator conductor, except for a switchboard with a draw out or plug-in type generator circuit breaker that disconnects:

(i)Each generator conductor; and

(ii)If there is a switch in the generator neutral, each ungrounded conductor; and

(3)An indicator light connected between the generator and circuit breaker.

(e)For each emergency generator that is not excited from a variable voltage or rotary amplifier exciter that is controlled by a voltage regulator unit acting on the exciter field, each emergency switchboard must have:

(1)A generator field rheostat;

(2)A double pole field switch;

(3)Discharge clips; and

(4)A discharge resistor.

(f)Each emergency switchboard must have the following:

(1)An ammeter with a selector switch that connects the ammeter to show the current for each phase.

(2)A voltmeter with a selector switch that connects the voltmeter to show:

(i)Generator voltage of each phase; and

(ii)Bus voltage of one phase.

(3)Ground detection that meets subpart 111.05 for the emergency lighting system.

(4)A frequency meter.

(5)An exciter field rheostat.

(6)A voltage regulator and a voltage regulator functional cut-out switch.

(g)Each direct-current emergency switchboard must have the:

(1)Equipment under § 111.30-27 (b) through (d); and

(2)Ground detection under subpart 111.05 for the emergency lighting system. [CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by CGD 94-108, 61 FR 28279, June 4, 1996; USCG-2020-0075, 88 FR 16361, Mar. 16, 2023]

From regulation to exam

See how this section shows up on the test

Try a sample question

According to 46 CFR, where must the neutral of a grounded generation and distribution system be grounded?

No sign-up needed.

Was this page helpful?

Start drilling in 30 seconds. Free.

No signup, no credit card — answer 5 real, cited exam questions right now.

46 CFR §111.30-29 — -29 -29 Emergency switchboards · CaptainsGround