(a) All low voltage and medium voltage switchboards (as low and medium are determined within the standard used) must meet—

Section 111.30-5 — full text

Rendered cleanly from the source — the exact regulatory text, with subsection structure preserved.

(a)All low voltage and medium voltage switchboards (as low and medium are determined within the standard used) must meet—

(1)For low voltages, either section 6 (except section 6.3.3) of IEEE 45.7-2012 or of IEC 60092-302:1997 (both incorporated by reference; see § 110.10-1 of this subchapter), as appropriate.

(2)For medium voltages, either section 7 of IEEE 45.7-2012 or IEC 60092-503:2007 (incorporated by reference; see § 110.10-1 of this subchapter), as appropriate.

(b)Each switchboard must be fitted with a dripshield unless the switchboard is a deck-to-overhead mounted type which cannot be subjected to leaks or falling objects. [USCG-2020-0075, 88 FR 16361, Mar. 16, 2023]