-3 -3 Protection of conductors

The exact 46 CFR §111.50-3 text, rendered cleanly with its subsection structure — plus how this rule shows up on the exam.

Public-domain federal text · ingested from eCFR
Every answer cited & verifiedAll 4 USCG exam modulesReviewed by a former NMC exam writer

TL;DR

(a)The purpose of overcurrent protection for conductors is to open the electric circuit if the current reaches a value that will cause an excessive or dangerous temperature in the conductor or conductor insulation. A grounded conductor is protected from overcurrent if a protective device of a suitable rating or setting is in each ungrounded conductor of the same circuit.

Section 111.50-3 — full text

Rendered cleanly from the source — the exact regulatory text, with subsection structure preserved.

(a)The purpose of overcurrent protection for conductors is to open the electric circuit if the current reaches a value that will cause an excessive or dangerous temperature in the conductor or conductor insulation. A grounded conductor is protected from overcurrent if a protective device of a suitable rating or setting is in each ungrounded conductor of the same circuit. (b)Each conductor must be protected in accordance with its current carrying capacity, except a conductor for the following circuits which must meet the following listed subparts:

(1)Propulsion circuits, subpart 111.35.

(2)Steering circuits, subpart 58.25 of this chapter.

(3)Motor circuits, subpart 111.70.

(4)Flexible cord and fixture wire for lighting circuits, subpart 111.75.

(5)Switchboard circuits, subpart 111.30. (c)If the allowable current-carrying capacity of the conductor does not correspond to a standard rating for fuses or circuit breakers that meets Section 240.6 of NFPA 70 (incorporated by reference; see 46 CFR 110.10-1), then the next larger such rating is acceptable, except that:

(1)This rating must not be larger than 150 percent of the current-carrying capacity of the conductor; and

(2)The effect of temperature on the operation of fuses and thermally controlled circuit breakers must be taken into consideration. (d)An overcurrent protective device must not be connected in parallel with another overcurrent protective device. (e)No thermal cutout, thermal relay, or other device not designed to open a short circuit may be used for protection of a conductor against overcurrent due to a short circuit or ground, except in a motor circuit as described in Article 430 of NFPA 70 or in IEC 60092-202:2016 (both incorporated by reference; see § 110.10-1 of this subchapter). (f)A fuse or overcurrent trip unit of a circuit breaker must be in each ungrounded conductor. A branch switch or circuit breaker must open all conductors of the circuit, except grounded conductors. (g)An overcurrent device must not be in a permanently grounded conductor, except:

(1)An overcurrent device that simultaneously opens all conductors of the circuit, unless prohibited by § 111.05-17 for the bus-tie feeder connecting the emergency and main switchboards; and

(2)For motor-running protection described in Article 430 of NFPA 70 or in IEC 60092-202:2016 (both incorporated by reference; see § 110.10-1 of this subchapter). [CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by CGD 94-108, 61 FR 28279, June 4, 1996; CGD 97-057, 62 FR 51047, Sept. 30, 1997; USCG-2003-16630, 73 FR 65197, Oct. 31, 2008; USCG-2013-0671, 78 FR 60153, Sept. 30, 2013; USCG-2020-0075, 88 FR 16362, Mar. 16, 2023]

(1)Propulsion circuits, subpart 111.35.

(2)Steering circuits, subpart 58.25 of this chapter.

(3)Motor circuits, subpart 111.70.

(4)Flexible cord and fixture wire for lighting circuits, subpart 111.75.

(5)Switchboard circuits, subpart 111.30. (c)If the allowable current-carrying capacity of the conductor does not correspond to a standard rating for fuses or circuit breakers that meets Section 240.6 of NFPA 70 (incorporated by reference; see 46 CFR 110.10-1), then the next larger such rating is acceptable, except that:

(1)This rating must not be larger than 150 percent of the current-carrying capacity of the conductor; and

(2)The effect of temperature on the operation of fuses and thermally controlled circuit breakers must be taken into consideration. (d)An overcurrent protective device must not be connected in parallel with another overcurrent protective device. (e)No thermal cutout, thermal relay, or other device not designed to open a short circuit may be used for protection of a conductor against overcurrent due to a short circuit or ground, except in a motor circuit as described in Article 430 of NFPA 70 or in IEC 60092-202:2016 (both incorporated by reference; see § 110.10-1 of this subchapter). (f)A fuse or overcurrent trip unit of a circuit breaker must be in each ungrounded conductor. A branch switch or circuit breaker must open all conductors of the circuit, except grounded conductors. (g)An overcurrent device must not be in a permanently grounded conductor, except:

(1)An overcurrent device that simultaneously opens all conductors of the circuit, unless prohibited by § 111.05-17 for the bus-tie feeder connecting the emergency and main switchboards; and

(2)For motor-running protection described in Article 430 of NFPA 70 or in IEC 60092-202:2016 (both incorporated by reference; see § 110.10-1 of this subchapter). [CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by CGD 94-108, 61 FR 28279, June 4, 1996; CGD 97-057, 62 FR 51047, Sept. 30, 1997; USCG-2003-16630, 73 FR 65197, Oct. 31, 2008; USCG-2013-0671, 78 FR 60153, Sept. 30, 2013; USCG-2020-0075, 88 FR 16362, Mar. 16, 2023]

From regulation to exam

See how this section shows up on the test

Test your knowledge

Try 5 real exam questions on the rules behind this regulation — no sign-up needed.

Was this page helpful?

Start drilling in 30 seconds. Free.

No signup, no credit card — answer 5 real, cited exam questions right now.

46 CFR §111.50-3 — -3 -3 Protection of conductors · CaptainsGround