-5 -5 Location of overcurrent protective devices

The exact 46 CFR §111.50-5 text, rendered cleanly with its subsection structure — plus how this rule shows up on the exam.

Public-domain federal text · ingested from eCFR
Every answer cited & verifiedAll 4 USCG exam modulesReviewed by a former NMC exam writer

TL;DR

(a)Overcurrent devices must be at the point where the conductor to be protected receives its supply, except as follows:

Section 111.50-5 — full text

Rendered cleanly from the source — the exact regulatory text, with subsection structure preserved.

(a)Overcurrent devices must be at the point where the conductor to be protected receives its supply, except as follows:

(1)The generator overcurrent protective device must be on the ship's service generator switchboard. (See § 111.12-11(g) for additional requirements.)

(2)The overcurrent protection for the shore connection conductors must meet § 111.30-25(f).

(3)If the overcurrent device that protects the larger conductors also protects the smaller conductors, an overcurrent device is not required at the supply to the smaller conductors.

(4)If the overcurrent device protecting the primary side of a transformer also protects the conductors connected to the secondary side, as determined by multiplying the current-carrying capacity of the secondary conductor by the secondary to primary transformer voltage ratio, and this protection meets § 111.20-15 of this chapter, an overcurrent device is not required at the supply to the secondary side conductors. (b)Each overcurrent device:

(1)Must be:

(i)Readily accessible; and

(ii)In a distribution panelboard, switchboard, motor controller, or similar enclosure; and

(2)Must not be:

(i)Exposed to mechanical damage; and

(ii)Near an easily ignitable material or where explosive gas or vapor may accumulate. [CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by USCG-2020-0075, 88 FR 16362, Mar. 16, 2023]

(1)The generator overcurrent protective device must be on the ship's service generator switchboard. (See § 111.12-11(g) for additional requirements.)

(2)The overcurrent protection for the shore connection conductors must meet § 111.30-25(f).

(3)If the overcurrent device that protects the larger conductors also protects the smaller conductors, an overcurrent device is not required at the supply to the smaller conductors.

(4)If the overcurrent device protecting the primary side of a transformer also protects the conductors connected to the secondary side, as determined by multiplying the current-carrying capacity of the secondary conductor by the secondary to primary transformer voltage ratio, and this protection meets § 111.20-15 of this chapter, an overcurrent device is not required at the supply to the secondary side conductors. (b)Each overcurrent device:

(1)Must be:

(i)Readily accessible; and

(ii)In a distribution panelboard, switchboard, motor controller, or similar enclosure; and

(2)Must not be:

(i)Exposed to mechanical damage; and

(ii)Near an easily ignitable material or where explosive gas or vapor may accumulate. [CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by USCG-2020-0075, 88 FR 16362, Mar. 16, 2023]

From regulation to exam

See how this section shows up on the test

Test your knowledge

Try 5 real exam questions on the rules behind this regulation — no sign-up needed.

Was this page helpful?

Start drilling in 30 seconds. Free.

No signup, no credit card — answer 5 real, cited exam questions right now.

46 CFR §111.50-5 — -5 -5 Location of overcurrent protective devices · CaptainsGround