-2 -2 Short-circuit calculations

The exact 46 CFR §111.51-2 text, rendered cleanly with its subsection structure — plus how this rule shows up on the exam.

Public-domain federal text · ingested from eCFR
Every answer cited & verifiedAll 4 USCG exam modulesReviewed by a former NMC exam writer

TL;DR

(1) From the aggregate contribution of all generators that can simultaneously operate in parallel;

Section 111.51-2 — full text

Rendered cleanly from the source — the exact regulatory text, with subsection structure preserved.

(a)The available short-circuit current must be computed—

(1)From the aggregate contribution of all generators that can simultaneously operate in parallel;

(2)From the largest probable motor load; and

(3)With a three-phase fault on the load terminals of the protective device.

(b)The calculated currents must be used to select suitably rated equipment and to allow the selection and setting of protective devices.