-5 -5 Protection of vital equipment

The exact 46 CFR §111.51-5 text, rendered cleanly with its subsection structure — plus how this rule shows up on the exam.

Public-domain federal text · ingested from eCFR
Every answer cited & verifiedAll 4 USCG exam modulesReviewed by a former NMC exam writer

TL;DR

(a) The coordination of overcurrent protective devices must be demonstrated for all potential plant configurations.

Section 111.51-5 — full text

Rendered cleanly from the source — the exact regulatory text, with subsection structure preserved.

(a)The coordination of overcurrent protective devices must be demonstrated for all potential plant configurations.

(b)Protective relays and overcurrent protective devices must be installed so that:

(1)A short-circuit on a circuit that is not vital to the propulsion, control, or safety of the vessel does not trip equipment that is vital; and

(2)A short-circuit on a circuit that is vital to the propulsion, control, or safety of the vessel is cleared only by the protective device that is closest to the point of the short-circuit.