(1) Meet the general provisions of Article 240 of NFPA 70 or IEC 60092-202:2016 (both incorporated by reference; see “§ 110.10-1 of this subchapter) as appropriate.

Section 111.53-1 — full text

Rendered cleanly from the source — the exact regulatory text, with subsection structure preserved.

(a)Each fuse must—

(1)Meet the general provisions of Article 240 of NFPA 70 or IEC 60092-202:2016 (both incorporated by reference; see “§ 110.10-1 of this subchapter) as appropriate.

(2)Have an interrupting rating sufficient to interrupt the asymmetrical RMS short-circuit current at the point of application; and

(b)Renewable link cartridge-type fuses must not be used.

(c)Each fuse installation must provide for ready access to test the condition of the fuse. [CGD 94-108, 61 FR 28279, June 4, 1996, as amended by61 FR 33045, June 26, 1996; USCG-2003-16630, 73 FR 65197, Oct. 31, 2008; USCG-2013-0671, 78 FR 60153, Sept. 30, 2013; USCG-2020-0075, 88 FR 16363, Mar. 16, 2023]