(a)Each flexible cord and cable must meet the requirements in Sections 4.4.2. and 4.4.6 of IEEE 45.8-2016, Article 400 of NFPA 70, ANSI/NEMA WC-70, or ANSI/UL 62 (all incorporated by reference; see § 110.10-1 of this subchapter).

Section 111.60-13 — full text

Rendered cleanly from the source — the exact regulatory text, with subsection structure preserved.

(a)Each flexible cord and cable must meet the requirements in Sections 4.4.2. and 4.4.6 of IEEE 45.8-2016, Article 400 of NFPA 70, ANSI/NEMA WC-70, or ANSI/UL 62 (all incorporated by reference; see § 110.10-1 of this subchapter). (b)No flexible cord may be used except:

(1)As allowed under Sections 400.10 and 400.12 of NFPA 70; and

(2)In accordance with Table 400.4 in NFPA 70. (c)No flexible cord may carry more current than allowed under Table 400.5 in NFPA 70, or ANSI/NEMA WC-70. (d)Each flexible cord must be 18 AWG (0.82 mm2) or larger. (e)Each flexible cord and cable must be without splices or taps except for a cord or cable 12 AWG (3.3 mm2) or larger spliced for repairs in accordance with § 111.60-19. (f)Each flexible cord and cable must be connected to a device or fitting by a knot, tape, or special fitting so that tension is not transmitted to joints or terminal screws. [CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by CGD 94-108, 61 FR 28281, June 4, 1996; USCG-2003-16630, 73 FR 65198, Oct. 31, 2008; USCG-2020-0075, 88 FR 16364, Mar. 16, 2023]

(1)As allowed under Sections 400.10 and 400.12 of NFPA 70; and

(2)In accordance with Table 400.4 in NFPA 70. (c)No flexible cord may carry more current than allowed under Table 400.5 in NFPA 70, or ANSI/NEMA WC-70. (d)Each flexible cord must be 18 AWG (0.82 mm2) or larger. (e)Each flexible cord and cable must be without splices or taps except for a cord or cable 12 AWG (3.3 mm2) or larger spliced for repairs in accordance with § 111.60-19. (f)Each flexible cord and cable must be connected to a device or fitting by a knot, tape, or special fitting so that tension is not transmitted to joints or terminal screws. [CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by CGD 94-108, 61 FR 28281, June 4, 1996; USCG-2003-16630, 73 FR 65198, Oct. 31, 2008; USCG-2020-0075, 88 FR 16364, Mar. 16, 2023]

From regulation to exam

See how this section shows up on the test

Test your knowledge

Try 5 real exam questions on the rules behind this regulation — no sign-up needed.

Was this page helpful?

Start drilling in 30 seconds. Free.

No signup, no credit card — answer 5 real, cited exam questions right now.

46 CFR §111.60-13 — -13 -13 Flexible electric cord and cables · CaptainsGround