Interconnected detection and alarm system

The exact 46 CFR §181.450 text, rendered cleanly with its subsection structure — plus how this rule shows up on the exam.

Public-domain federal text · ingested from eCFR
Every answer cited & verifiedAll 4 USCG exam modulesReviewed by a former NMC exam writer

TL;DR

(1) Consist of multiple-station smoke detectors listed by an NRTL, or independent laboratory accepted by the Commandant according to 46 CFR subpart 159.010, as meeting UL 217 (incorporated by reference, see 46 CFR 175.600);

Section 181.450 — full text

Rendered cleanly from the source — the exact regulatory text, with subsection structure preserved.

(a)An interconnected detection and alarm system must:

(1)Consist of multiple-station smoke detectors listed by an NRTL, or independent laboratory accepted by the Commandant according to 46 CFR subpart 159.010, as meeting UL 217 (incorporated by reference, see 46 CFR 175.600);

(2)Be installed such that the actuation of alarm in one area results in both audible and visual alarms in all areas required by 46 CFR 181.405(c) or 118.400(d) to be protected by the interconnected detection and alarm system;

(3)Contain an independent power source; and

(4)Alarm on low power.

(b)A fire detection and alarm system of an approved type installed in accordance with 46 CFR part 76 would satisfy the requirements of this section. [USCG-2021-0306, 86 FR 73172, Dec. 27, 2021]

From regulation to exam

See how this section shows up on the test

Test your knowledge

Try 5 real exam questions on the rules behind this regulation — no sign-up needed.

Start drilling in 30 seconds. Free.

No signup, no credit card — answer 5 real, cited exam questions right now.

46 CFR §181.450 — Interconnected detection and alarm system · CaptainsGround