Required number, type, and location

The exact 46 CFR §181.500 text, rendered cleanly with its subsection structure — plus how this rule shows up on the exam.

Public-domain federal text · ingested from eCFR
Every answer cited & verifiedAll 4 USCG exam modulesReviewed by a former NMC exam writer

TL;DR

(a) Each portable fire extinguisher on a vessel must be of an approved type. The minimum number of portable fire extinguishers required on a vessel must be acceptable to the cognizant Officer in Charge, Marine Inspection, but must not be fewer than the minimum number required by table 1 to § 181.500(b) and other provisions of this section.

Section 181.500 — full text

Rendered cleanly from the source — the exact regulatory text, with subsection structure preserved.

(a)Each portable fire extinguisher on a vessel must be of an approved type. The minimum number of portable fire extinguishers required on a vessel must be acceptable to the cognizant Officer in Charge, Marine Inspection, but must not be fewer than the minimum number required by table 1 to § 181.500(b) and other provisions of this section.

(b)Table 1 to § 181.500(b) indicates the minimum required classification for each space listed. Extinguishers with larger numerical ratings or multiple letter designations may be used if the extinguishers meet the requirements of the table.

(c)A vehicle deck without a fixed sprinkler system and exposed to weather must have one 40-B portable fire extinguisher for every five vehicles, located near an entrance to the space.

(d)The frame or support of each semi-portable fire extinguisher permitted by paragraph (a) of this section must be welded or otherwise permanently attached to a bulkhead or deck. Table 1 to § 181.500()—Required Portable Fire Extinguishers Space | Portable fire extinguishers Minimumrequiredrating | Quantity and location Operating Station | 10-B:C | 1. Machinery Space | 40-B:C | 1 in the vicinity of the exit. Open Vehicle Deck | 40-B | 1 for every 10 vehicles. Accommodation Space | 2-A | 1 each for each 2,500 square feet (232.3 square meters) or fraction thereof. Galley | 40-B:C | 1. Pantry, concession stand | 2-A | 1 in the vicinity of the exit. [USCG-2012-0196, 81 FR 48300, July 22, 2016, as amended by USCG-2020-0519, 89 FR 76707, Sept. 18, 2024]

From regulation to exam

See how this section shows up on the test

Test your knowledge

Try 5 real exam questions on the rules behind this regulation — no sign-up needed.

Start drilling in 30 seconds. Free.

No signup, no credit card — answer 5 real, cited exam questions right now.

46 CFR §181.500 — Required number, type, and location · CaptainsGround