(a) A water heater must meet the requirements of parts 53 and 63 of this chapter if rated at not more than 689 kPa (100 psig) and 121 °C (250 °F), except that an electric water heater is also acceptable if it:

Section 182.320 — full text

Rendered cleanly from the source — the exact regulatory text, with subsection structure preserved.

(a)A water heater must meet the requirements of parts 53 and 63 of this chapter if rated at not more than 689 kPa (100 psig) and 121 °C (250 °F), except that an electric water heater is also acceptable if it:

(1)Has a capacity of not more than 454 liters (120 gallons);

(2)Has a heat input of not more than 58.6 kilowatts (200,000 Btu per hour);

(3)Is listed under UL 174, UL 1453 (both incorporated by reference; see 46 CFR 175.600) or other standard specified by the Commandant; and

(4)Is protected by a pressure-temperature relief device.

(b)A water heater must meet the requirements of parts 52 and 63 of this chapter if rated at more than 689 kPa (100 psig) or 121 °C (250 °F).

(c)A water heater must be installed and secured from rolling by straps or other devices to the satisfaction of the cognizant OCMI. [CGD 85-080, 61 FR 986, Jan. 10, 1996; 61 FR 20557, May 7, 1996, as amended at 62 FR 51358, Sept. 30, 1997; USCG-2003-16630, 73 FR 65207, Oct. 31, 2008]