(a) A dual voltage generator installed on a vessel shall be of the grounded type, where:

Section 183.324 — full text

Rendered cleanly from the source — the exact regulatory text, with subsection structure preserved.

(a)A dual voltage generator installed on a vessel shall be of the grounded type, where:

(1)The neutral of a dual voltage system must be solidly connected at the switchboard's neutral bus; and

(2)The neutral bus shall be connected to ground.

(b)The neutral of a dual voltage system must be accessible for checking the insulation resistance of the generator to ground before the generator is connected to the bus.

(c)Ground detection must be provided that:

(1)For an alternating current system, meets § 111.05-27 in subchapter J of this chapter; and

(2)For a direct current system, meets § 111.05-29 in subchapter J of this chapter.