-40 -40 Blowoff piping (replaces 122.1.4)

The exact 46 CFR §56.50-40 text, rendered cleanly with its subsection structure — plus how this rule shows up on the exam.

Public-domain federal text · ingested from eCFR
Every answer cited & verifiedAll 4 USCG exam modulesReviewed by a former NMC exam writer

TL;DR

(a)(1) The owner or operator of a vessel must follow the requirements for blowoff piping in this section instead of the requirements in 122.1.4 of ASME B31.1 (incorporated by reference; see § 56.01-2).

Section 56.50-40 — full text

Rendered cleanly from the source — the exact regulatory text, with subsection structure preserved.

(a)(1) The owner or operator of a vessel must follow the requirements for blowoff piping in this section instead of the requirements in 122.1.4 of ASME B31.1 (incorporated by reference; see § 56.01-2).

(2)Where blowoff valves are connected to a common discharge from two or more boilers, a nonreturn valve must be provided in the line from each boiler to prevent accidental blowback in the event the boiler blowoff valve is left open.

(b)Blowoff must be designed for not less than 125 percent of the maximum allowable working pressure of the boiler, or the maximum allowable working pressure of the boiler plus 225 psig, whichever is less. The value of allowable stress for design purposes must be selected as described in § 56.07-10(e) at a temperature not below that of saturated steam at the maximum allowable working pressure of the boiler.

(c)Boiler blowoff piping which discharges above the lightest loadline of a vessel must be arranged so that the discharge is deflected downward.

(d)Globe valves must not be used for blowoff service. [CGFR 68-82, 33 FR 18843, Dec. 18, 1968, as amended by CGFR 69-127, 35 FR 9978, June 17, 1970; CGD 73-254, 40 FR 40165, Sept. 2, 1975; USCG-2003-16630, 73 FR 65178, Oct. 31, 2008]

(2)Where blowoff valves are connected to a common discharge from two or more boilers, a nonreturn valve must be provided in the line from each boiler to prevent accidental blowback in the event the boiler blowoff valve is left open.

(b)Blowoff must be designed for not less than 125 percent of the maximum allowable working pressure of the boiler, or the maximum allowable working pressure of the boiler plus 225 psig, whichever is less. The value of allowable stress for design purposes must be selected as described in § 56.07-10(e) at a temperature not below that of saturated steam at the maximum allowable working pressure of the boiler.

(c)Boiler blowoff piping which discharges above the lightest loadline of a vessel must be arranged so that the discharge is deflected downward.

(d)Globe valves must not be used for blowoff service. [CGFR 68-82, 33 FR 18843, Dec. 18, 1968, as amended by CGFR 69-127, 35 FR 9978, June 17, 1970; CGD 73-254, 40 FR 40165, Sept. 2, 1975; USCG-2003-16630, 73 FR 65178, Oct. 31, 2008]

From regulation to exam

See how this section shows up on the test

Test your knowledge

Try 5 real exam questions on the rules behind this regulation — no sign-up needed.

Was this page helpful?

Start drilling in 30 seconds. Free.

No signup, no credit card — answer 5 real, cited exam questions right now.

46 CFR §56.50-40 — -40 -40 Blowoff piping (replaces 122.1.4) · CaptainsGround