-5 -5 Fired thermal fluid heaters

The exact 46 CFR §63.25-5 text, rendered cleanly with its subsection structure — plus how this rule shows up on the exam.

Public-domain federal text · ingested from eCFR
Every answer cited & verifiedAll 4 USCG exam modulesReviewed by a former NMC exam writer

TL;DR

(a)Fired thermal fluid heaters must meet the requirements of part 52 of this subchapter, as applicable.

Section 63.25-5 — full text

Rendered cleanly from the source — the exact regulatory text, with subsection structure preserved.

(a)Fired thermal fluid heaters must meet the requirements of part 52 of this subchapter, as applicable. (b)Fired thermal fluid heaters must have a low fluid level cutout device or a low flow device. When the rate of fluid flow through the heating coils is insufficient to ensure proper heat transfer, the device must cut off the fuel supply to the burner. If the fluid temperature exceeds the designed maximum operating temperature, a high temperature limit device must cut off the fuel supply to the burner. These devices must be of the manual reset type. [CGD 88-057, 55 FR 24238, June 15, 1990, as amended by USCG-2020-0634, 89 FR 50198, June 12, 2024]