Under 46 CFR §61.40-10, when a test of a monitored system would damage equipment or endanger personnel, which technique is acceptable as an alternative?

  1. A. Mis-adjustment of the monitored system to simulate the alarm condition
  2. B. Revision of system wiring to produce the desired signal
  3. Application of a synthesized signal to the sensor, provided the test equipment is maintained and periodically calibrated to the satisfaction of the OCMICorrect
  4. D. Bypassing the sensor entirely and manually tripping the alarm relay

Why C is correct

46 CFR §61.40-10(b) prohibits simulating monitored conditions by mis-adjustment, artificial signals, improper wiring, or tampering except when the test would damage equipment or endanger personnel. In that case, a synthesized signal applied to the sensor is acceptable if the test equipment is maintained in good working order and periodically calibrated to the OCMI's satisfaction.