Skip to main content
CaptainsGround
Every answer cited & verifiedAll 4 USCG exam modulesReviewed by a former NMC exam writer
USCG Exam PracticeRefrigeration principles and systems

What safety system does 46 CFR §58.20-15 require in a machinery compartment that contains ammonia refrigeration equipment?

  1. A. A fixed CO2 fire-suppression system with a remote release station outside the compartment.
  2. A sprinkler system providing effective water spray with a remote-control device located outside the compartment.Correct
  3. C. An exhaust ventilation system capable of 30 air changes per hour, activated automatically on gas detection.
  4. D. A halon total-flooding system interlocked with the compressor shutdown circuit.

Why B is correct

46 CFR §58.20-15(b) specifically requires machinery compartments containing ammonia equipment to be fitted with a sprinkler system providing effective water spray, with the remote-control device located outside the compartment. The regulation does not prescribe CO2, halon, or a specific ventilation change rate for this purpose.

More Refrigeration principles and systems questions

Start drilling in 30 seconds. Free.

No signup, no credit card — answer 5 real, cited exam questions right now.

What safety system does 46 CFR §58.20-15 require in a machinery com… — USCG Exam Practice · CaptainsGround