For gasoline fuel systems under 46 CFR §56.50-70, vent pipes on fuel tanks must terminate at what minimum height above the weather deck, and at what minimum distance from any opening into living quarters?

  1. A. At least 3 feet above the weather deck and not less than 2 feet from any opening into living quarters
  2. At least 2 feet above the weather deck and not less than 3 feet from any opening into living quartersCorrect
  3. C. At least 2 feet above the weather deck and not less than 2 feet from any opening into living quarters
  4. D. At least 3 feet above the weather deck and not less than 3 feet from any opening into living quarters

Why B is correct

46 CFR §56.50-70(h) states vent pipes must terminate at least 2 feet above the weather deck and not less than 3 feet from any opening into living quarters or other below-deck space. The two distances are not interchangeable.