Under 46 CFR §56.50-30, what design pressure must feed piping from the boiler — to and including the required stop and stop-check valves — be rated for, relative to the boiler's maximum allowable working pressure (MAWP)?

  1. A. Equal to the MAWP of the boiler
  2. Exceeding the MAWP by either 25 percent or 225 psig, whichever is lessCorrect
  3. C. Exceeding the MAWP by either 25 percent or 225 psig, whichever is greater
  4. D. Equal to the feed pump relief valve setting regardless of boiler MAWP

Why B is correct

46 CFR §56.50-30(a)(3) specifies that feed piping from the boiler, to and including the required stop and stop-check valves, must have a design pressure that exceeds the MAWP of the boiler by either 25 percent or 225 psig, whichever is less. The 'whichever is greater' option would impose a more severe requirement than the regulation states.