A generator rated for 40 °C ambient is installed in a machinery space where ambient temperature regularly reaches 50 °C. Under 46 CFR §183.320, what action is required?

  1. A. The generator must be replaced with one rated for 50 °C
  2. The generator may be used if derated to 80 percent of full load rating and overcurrent devices are adjusted accordinglyCorrect
  3. C. The generator may be used at full rating provided additional ventilation is supplied
  4. D. The generator must be derated to 70 percent of full load rating

Why B is correct

46 CFR §183.320(b)(2) permits a 40 °C-rated generator to be used in a 50 °C ambient location provided it is derated to 80 percent of its full load rating and the rating or setting of overcurrent devices is reduced accordingly.