A generator rated for 40 °C ambient is installed in a space where the ambient temperature regularly reaches 50 °C. Under 46 CFR §183.320, what corrective action is required?

  1. A. The generator must be replaced with one rated for 50 °C; no derating is permitted
  2. The generator may be used if derated to 80 percent of full load rating and overcurrent devices are adjusted accordinglyCorrect
  3. C. The generator may be used at full rating provided additional ventilation is supplied
  4. D. The generator must be derated to 50 percent of full load rating to account for the temperature difference

Why B is correct

46 CFR §183.320(b)(2) permits a generator designed for 40 °C to be used in a 50 °C ambient location provided it is derated to 80 percent of the full load rating and the rating or setting of the overcurrent devices is reduced accordingly.