Under 46 CFR §111.05-17, which of the following correctly describes the grounding arrangement for the neutral of an emergency power generation system?

  1. A. The neutral must be directly grounded at the emergency switchboard and isolated from the main switchboard neutral bus.
  2. The neutral must have no direct ground at the emergency switchboard, and the neutral bus must be permanently connected to the main switchboard neutral bus.Correct
  3. C. The neutral must be grounded at both the emergency switchboard and the main switchboard simultaneously.
  4. D. The neutral must be grounded through a fuse at the emergency switchboard to protect against fault current.

Why B is correct

46 CFR §111.05-17(a)(1) and (2) require that the emergency system neutral have no direct ground at the emergency switchboard and that its neutral bus be permanently connected to the main switchboard neutral bus. A direct ground at the emergency switchboard and simultaneous dual grounding are both prohibited by this section.