Under 46 CFR §111.05-37, under what condition may an overcurrent device be installed in a permanently grounded conductor?

  1. A. When the overcurrent device is a fuse rated at 125% of the conductor ampacity
  2. When the overcurrent device simultaneously opens each ungrounded conductor of the circuitCorrect
  3. C. When the grounded conductor is part of the emergency-main switchboard bus-tie
  4. D. When the overcurrent device is a ground fault circuit interrupter rated for marine use

Why B is correct

46 CFR §111.05-37(a) prohibits an overcurrent device in a permanently grounded conductor unless that device simultaneously opens each ungrounded conductor of the circuit. The neutral of the emergency-main switchboard bus-tie is specifically prohibited from having any switch or circuit breaker under §111.05-37(b).