In an ungrounded three-phase AC system aboard a vessel, how many motor-running protective devices (overload coil or heater type relay) are required per 46 CFR §111.70-1, and where must they be placed?

  1. Two devices, placed in any two ungrounded conductorsCorrect
  2. B. Three devices, one in each ungrounded conductor
  3. C. Two devices, placed in the two grounded conductors
  4. D. One device, placed in the highest-current ungrounded conductor

Why A is correct

46 CFR §111.70-1(b) states that in ungrounded three-phase AC systems, only two motor-running protective devices need be used, placed in any two ungrounded conductors. The exception applies when a wye-delta or delta-wye transformer is used.