Skip to main content
CaptainsGround
Every answer cited & verifiedAll 4 USCG exam modulesReviewed by a former NMC exam writer
USCG Exam PracticeMotor controllers and remote control

Under 46 CFR §111.70-7, when a control, interlock, or indicator circuit cannot be energized from the load side of the motor disconnect device and its voltage exceeds 24 volts, one permissible alternative is to use a separate independent disconnect device for the control circuit. What additional requirement applies to that arrangement?

  1. The two independent disconnect devices must be adjacent to each other, and a fixed warning sign must be on the exterior door of the main disconnect deviceCorrect
  2. B. The control circuit disconnect must be interlocked so it opens automatically whenever the main motor disconnect is opened
  3. C. The control circuit disconnect must be located in a separate compartment from the motor disconnect to prevent simultaneous access
  4. D. A nameplate warning that opening the door will trip a vital auxiliary off-line must be affixed to the controller door

Why A is correct

46 CFR §111.70-7(d)(1) requires that when a separate independent disconnect is used for the control circuit, the two devices must be adjacent to each other and a fixed sign warning the operator to open both devices must appear on the exterior of the main disconnect door. The nameplate warning in option D applies to the door-actuated disconnect arrangement under §111.70-7(d)(2), not the independent device arrangement.

More Motor controllers and remote control questions

Start drilling in 30 seconds. Free.

No signup, no credit card — answer 5 real, cited exam questions right now.

Under 46 CFR §111.70-7, when a control, interlock, or indicator cir… — USCG Exam Practice · CaptainsGround