Skip to main content
CaptainsGround
Every answer cited & verifiedAll 4 USCG exam modulesReviewed by a former NMC exam writer
USCG Exam PracticeMotor controllers and remote control

Under 46 CFR §111.70-7, when a control, interlock, or indicator circuit cannot be powered from the load side of the disconnect device and its voltage exceeds 24 volts, one acceptable alternative is to use a disconnect device actuated by the opening of the controller door. Which additional requirement applies when this arrangement is used for a vital auxiliary circuit?

  1. A. A fixed sign warning to open both disconnect devices must be posted on the exterior of the main disconnect door
  2. The disconnect device and its connections must have no electrically uninsulated or unshielded surface, and a nameplate warning that opening the door will trip the vital auxiliary off-line must be affixed to the doorCorrect
  3. C. The control circuit voltage must be reduced to 24 volts or less before the door-actuated disconnect is permitted
  4. D. An independent overcurrent device rated at not more than 300 percent of conductor capacity must be installed in each side of the control circuit

Why B is correct

46 CFR §111.70-7(d)(2) requires that when a door-actuated disconnect is used, the disconnect device and its connections including terminal blocks must have no electrically uninsulated or unshielded surface. Additionally, when used for vital auxiliary circuits, a nameplate warning that opening the door will trip the vital auxiliary off-line must be affixed to the controller door. Option A describes the alternative method in §111.70-7(d)(1), not (d)(2).

More Motor controllers and remote control questions

Start drilling in 30 seconds. Free.

No signup, no credit card — answer 5 real, cited exam questions right now.

Under 46 CFR §111.70-7, when a control, interlock, or indicator cir… — USCG Exam Practice · CaptainsGround