USCG Exam PracticeMotor controllers and remote control

In an ungrounded three-phase AC system, how many motor-running protective devices are required per 46 CFR §111.70-1, and where must they be placed?

  1. A. Three devices, one in each ungrounded conductor
  2. Two devices, in any two ungrounded conductorsCorrect
  3. C. One device, in the grounded neutral conductor
  4. D. Two devices, one in the grounded conductor and one in an ungrounded conductor

Why B is correct

46 CFR §111.70-1(b) specifies that in ungrounded three-phase AC systems, only two motor-running protective devices need be used, placed in any two ungrounded conductors. This exception does not apply when a wye-delta or delta-wye transformer is used.