On a shipboard ungrounded delta distribution system, the ground-detection lamp associated with a faulted phase will:

  1. A. Brighten, while the lamps on the unfaulted phases dim
  2. B. Extinguish completely, while the lamps on the unfaulted phases remain unchanged
  3. Dim or go out, while the lamps on the unfaulted phases brightenCorrect
  4. D. Flicker at the system frequency, indicating the location of the fault

Why C is correct

In a three-lamp ground-detection scheme on an ungrounded system, all lamps normally glow equally. A ground on one phase reduces that phase's voltage-to-ground toward zero, dimming or extinguishing that lamp, while the other two phases see elevated voltage-to-ground, brightening their lamps.