A current transformer (CT) is installed on a high-current bus to feed the switchboard ammeter. While the bus is energized, a technician removes the ammeter for calibration without first shorting the CT secondary terminals. What is the immediate hazard?

  1. A. The CT primary winding will overheat and fail because current has no return path
  2. A lethal high voltage will develop across the open CT secondary terminalsCorrect
  3. C. The bus voltage will collapse because the CT provides the reference for the protection relays
  4. D. The ammeter will be permanently magnetized when reconnected because of residual flux

Why B is correct

With primary current flowing, an open CT secondary forces all the magnetic flux to drive a voltage across the open secondary terminals; this voltage can reach lethal levels. The CT secondary must always be short-circuited before any secondary device is disconnected.