A compartment above the weather deck contains gas-consuming appliances and is fitted with natural ventilation. Under 46 CFR §58.16-20, which arrangement satisfies the minimum regulatory requirement?

  1. A. One natural ventilator duct extending to the overhead, with the motor located inside the compartment
  2. Two natural ventilator ducts, one extending to the floor level and one to the overhead, with any powered ventilation motor located outside the compartmentCorrect
  3. C. Powered ventilation only, with capacity to change the air once every 6 minutes
  4. D. Two natural ventilator ducts, both extending to the overhead of the compartment

Why B is correct

46 CFR §58.16-20(a) requires at least two natural ventilator ducts — one extending to the floor level and one to the overhead — for above-deck compartments. If powered ventilation is used, the motor must be outside the compartment. A single duct, two ducts both at the overhead, or powered ventilation alone do not meet the stated requirements.