A permanently grounded conductor in a shipboard distribution system has an overcurrent device installed in it. Under 46 CFR §111.05-37, this installation is permissible only if which condition is met?

  1. A. The overcurrent device is rated at no more than 125 percent of the conductor's ampacity
  2. The overcurrent device simultaneously opens each ungrounded conductor of the circuitCorrect
  3. C. A ground fault indicator is installed on the same panel to detect neutral current
  4. D. The overcurrent device is a fuse rather than a circuit breaker to limit interrupting energy

Why B is correct

46 CFR §111.05-37(a) permits an overcurrent device on a permanently grounded conductor only if that device simultaneously opens each ungrounded conductor of the circuit. This prevents the neutral from being opened while ungrounded conductors remain energized, which would create a shock hazard.