Under 46 CFR §111.70-3, a motor controller for a fire pump must have low-voltage release rather than low-voltage protection under which condition?

  1. When automatic restart after a voltage failure or resumption of operation is not hazardousCorrect
  2. B. When the fire pump motor is less than 2 horsepower (1.5 kW)
  3. C. When the fire pump can be restarted from a central control station
  4. D. When the starting current of the fire pump exceeds the capacity of one ship's service generator

Why A is correct

46 CFR §111.70-3(b) requires low-voltage release for fire pump controllers when automatic restart after a voltage failure or its resumption to operation is not hazardous. If automatic restart is hazardous, low-voltage protection is required instead. The central control station exception applies to vital propulsion auxiliaries, not fire pumps.