Under 46 CFR §111.106-3, lighting circuits serving explosion-proof fixtures in an enclosed hazardous space must meet several requirements. Which of the following is specifically required?

  1. A. The circuit switch and overcurrent device must be located inside the hazardous space for rapid de-energization
  2. B. A single lighting branch circuit is sufficient provided it is rated for the full connected load
  3. The switch and overcurrent protective device must open all ungrounded conductors of the circuit simultaneouslyCorrect
  4. D. Lighting fixtures must be certified under IEC 60079-18 for Zone 0 locations

Why C is correct

46 CFR §111.106-3(e)(4) requires the switch and overcurrent protective device to open all ungrounded conductors simultaneously. §111.106-3(e)(3) further requires that the switch and overcurrent device NOT be located within the enclosed hazardous space, making option A incorrect. At least two branch circuits are required per §111.106-3(e)(1), making option B incorrect.