Before recharging a refrigeration system that has been opened for repair, the system must be evacuated to a deep vacuum. What is the primary technical reason for this requirement?

  1. A. Evacuation purges non-condensable nitrogen used during pressure testing before refrigerant is introduced
  2. B. Evacuation confirms the integrity of the pressure vessels in accordance with 46 CFR part 54
  3. Evacuation boils off residual moisture; water in the system freezes at the metering orifice and reacts with oil and refrigerant to form acids and sludgeCorrect
  4. D. Evacuation removes excess compressor oil that migrated to the low side during the repair, preventing liquid floodback on startup

Why C is correct

NAVEDTRA 14075 §6-6 identifies moisture as the enemy of any refrigerant: water freezes at the metering orifice and reacts with oil and refrigerant to form acids and sludge. Section §6-6 also states that a system opened for repair is evacuated to boil off all moisture before recharging. Filter-driers are fitted for the same reason.